Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization
NV Media Card
Operation
Onboard
PLC
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
202 Powerdrive F300 User Guide
Issue Number: 2
06.065 Standard Under Voltage Threshold ±VM_STD_UNDER_VOLTS
200 V drive: 175 V
400 V drive: 330 V
575 V drive: 435 V
690 V drive: 435 V
RW Num RA US
06.066 Low Voltage Under Voltage Threshold ±VM_LOW_UNDER_VOLTS
200 V drive: 175 V
400 V drive: 330 V
575 V drive: 435 V
690 V drive: 435 V
RW Num RA US
06.067 Low Under Voltage Threshold Select Off (0) or On (1) Off (0) RW Bit US
06.068 Back Up Supply Mode Enable Off (0) or On (1) Off (0) RW Bit US
06.069 Under-Voltage System Contactor Close Off (0) or On (1) RO Bit ND NC PT
06.070 Under-Voltage System Contactor Closed Off (0) or On (1) Off (0) RW Bit US
06.071 Slow Rectifier Charge Rate Enable Off (0) or On (1) Off (0) RW Bit US
06.072 User Supply Select Off (0) or On (1) Off (0) RW Bit US
06.084 Date And Time Offset ±24.00 Hours 0.00 Hours RW Num US
Parameter
Range(
Ú)Default(Ö)
Type
OL RFC-A / S OL RFC-A RFC-S
RW Read / Write RO Read only Num Number parameter Bit Bit parameter Txt Text string Bin Binary parameter FI Filtered
ND No default value NC Not copied PT Protected parameter RA Rating dependent US User save PS Power-down save DE Destination
IP IP address Mac Mac address Date Date parameter Time Time parameter SMP Slot,menu,parameter Chr Character parameter Ver Version number