Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization
NV Media Card
Operation
Onboard
PLC
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
Powerdrive F300 User Guide 233
Issue Number: 2
09402210 110 150 221 192 159 108 77
09402660 132 200 266 255 231 192 160 109 77
10403200 160 250 320 285 238 173 124
10403610 200 300 361 339 285 238 173 126
11404370 225 350 437 415 336 272
11404870 250 400 487
460
415 336 272
11405070 280 400 507
460
415 336 272
575 V
05500039 2.2 3.0 3.9
05500061 4.0 5.0 6.1
05500100 5.5 7.5 10
06500120 7.5 10.0 12
06500170 11.0 15.0 17 14.8
06500220 15.0 20.0 22 20.5 15
06500270 18.5 25.0 27 26.2 20 16
06500340 22.0 30.0 34 31 26.2 20 16.8
06500430 30.0 40.0 43 39.6 31 26.2 20 16.8
07500530 45 50 53 51.8 40.2 27.7 21.2
07500730 55 60 73 71.5 51.8 40.2 27.7 21.2
08500860 75 75 86 73.1 49.7 37.8
08501080 90 100 108 91.8 73.1 49.7 37.8
09501250 110 125 125 101 71 54
09501500 110 150 150 126 100 70 54
10502000 130 200 200 168 126 100 70 54
11502480 185 250 248 205 TBC TBC
11502880 225 300 288
252
209 TBC TBC
11503150 250 350 315
252
209 TBC TBC
690 V
07600230 18.5 25 23 21.2
07600300 22 30 30 27.9 21.2
07600360 30 40 36 28.1 21.2
07600460 37 50 46 40.5 28.1 21.2
07600520 45 60 52 51.5 40.6 28.1 21.2
07600730 55 75 73 71.5 51.8 40.6 28.1 21.2
08600860 75 100 86 72.2 49.7 37.8
08601080 90 125 108 91.8 72.4 49.7 37.8
09601250 110 150 125 100 71 54
09601550 132 175 155 126 100 71 54
10601720 160 200 172 169 126 100 71 55
10601970 185 250 197 154 114 75 55
11602250 200 250 225
209
TBC TBC
11602750 250 300 275
252 209
TBC TBC
11603050 280 400 305
252 209
TBC TBC
Model
Normal Duty
Nominal rating
Maximum permissible continuous output current (A) for the following switching
frequencies
kW hp
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz