Powerdrive F300 User Guide 247
Issue Number: 2
Table 12-17 AC Input current and fuse ratings (690 V)
* Class aR fuses do not provide branch circuit protection. Ensure that the input cables are suitably protected using HRC fuses or breaker.
** These fuses are fast acting.
Ensure cables used suit local wiring regulations.
Model
Typical
input
current
Maximum
continuous
input
current
Maximum
overload
input
current
Fuse rating
IEC UL / USA
Nominal Maximum
Class
Nominal Maximum
Class
AAA A A A A
07600230
18
20 32 25
50
gG
25
50
CC, J
or T**
07600300
23
26 41 32 30
07600360
28
31 49 40 35
07600460
36
39 65
50 50
07600520
40
44 75
80 80
07600730
57
62 92 80 80
08600860
74
83 121 125 125
gR
100 100
HSJ
08601080
92
104 165 160 160 150 150
09601250
124
149 194 150 150
gR
150 150
HSJ
09601550
145
171 226 200 200 200 200
10601720
180
202 268 225 225 gR 250 250
HSJ
10601970
202
225 313 250 250 aR* 250 250
11602250
225
256 379
400 400 gR 400 400 HSJ11602750
217
302 425
11603050
298
329 465
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.
NOTE
CAUTION

Table of Contents

Other manuals for Emerson Powerdrive F300