Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization
NV Media Card
Operation
Onboard
PLC
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
Powerdrive F300 User Guide 275
Issue Number: 2
SlotX Different Option module in option slot X has changed
204
209
214
The SlotX Different trip indicates that the option module in option slot X on the drive is a different type to that installed when
parameters were last saved on the drive. The reason for the trip can be identified by the sub-trip number.
Recommended actions:
• Turn off the power, ensure the correct option modules are installed in the correct option slots and re-apply the power.
• Confirm that the currently installed option module is correct, ensure option module parameters are set correctly and
perform a user save in Pr mm.000.
SlotX Error Option module in option slot X has detected a fault
202
207
212
The SlotX Error trip indicates that the option module in option slot X on the drive has detected an error. The reason for the
error can be identified by the sub-trip number.
Recommended actions:
• See relevant Option Module User Guide for details of the trip
SlotX HF Option module X hardware fault
200
205
210
The SlotX HF trip indicates that the option module in option slot X on the drive has indicated a hardware fault. The possible
causes of the trip can be identified by the sub-trip number.
Recommended actions:
• Ensure the option module is installed correctly
• Replace the option module
• Replace the drive
SlotX Not installed Option module in option slot X has been removed
203
208
213
The SlotX Not installed trip indicates that the option module in option slot X on the drive has been removed since the last
power up.
Recommended actions:
• Ensure the option module is installed correctly.
• Re-install the option module.
• To confirm that the removed option module is no longer required perform a save function in Pr mm.000.
SlotX Watchdog Option module watchdog function service error
201
206
211
The SlotX Watchdog trip indicates that the option module installed in Slot X has started the option watchdog function and
then failed to service the watchdog correctly.
Recommended actions:
• Replace the option module
Trip Diagnosis
Sub-trip Reason
1 No module was installed previously
2
A module with the same identifier is installed, but the set-up menu for this option slot has been
changed, and so default parameters have been loaded for this menu.
3
A module with the same identifier is installed, but the applications menu for this option slot has been
changed, and so default parameters have been loaded for this menu.
4
A module with the same identifier is installed, but the set-up and applications menu for this option slot
have been changed, and so default parameters have been loaded for these menus.
>99 Shows the identifier of the module previously installed.
Sub-trip Reason
1 The module category cannot be identified
2 All the required customized menu table information has not been supplied or the tables supplied are corrupt
3 There is insufficient memory available to allocate the comms buffers for this module
4 The module has not indicated that it is running correctly during drive power-up
5 Module has been removed after power-up or it has stopped working
6 The module has not indicated that it has stopped accessing drive parameters during a drive mode change
7 The module has failed to acknowledge that a request has been made to reset the drive processor
8 The drive failed to correctly read the menu table from the module during drive power up
9 The drive failed to upload menu tables from the module and timed out (5 s)