Table 12-16 AC Input current and fuse ratings (575 V)
Table 12-17 AC Input current and fuse ratings (690 V)
Model
Typical input
current
Maximum
continuous
input current
Maximum
overload input
current
Fuse rating
IEC UL / USA
Nominal Maximum
Class
Nominal Maximum
Class
AAAAA AA
05500030
4
47
10
20 gG
10
CC
or J
05500040
6
79
05500069
9
11 15 20 20
06500100
12
13 22 20
40
gG
20
30
CC
or J
06500150
17
19 33 32 25
06500190
22
24 41 40 30
06500230
26
29 50
50
63
35
5006500290
33
37 63 40
06500350
41
47 76 63 50
07500440
41
45 75 50 50
gG
50 50
CC
or J
07500550
57
62 94 80 80 80 80
08500630
74
83 121 125 125
gR
100 100
HSJ
08500860
92
104 165 160 160 150 150
Model
Typical
input
current
Maximum
continuous
input
current
Maximum
overload
input
current
Fuse rating
IEC UL / USA
Nominal Maximum
Class
Nominal Maximum
Class
AAA A A A A
07600190
18
20 32 25
50
gG
25
50
CC
or J
07600240
23
26 41 32 30
07600290
28
31 49 40 35
07600380
36
39 65
50 50
07600440
40
44 75
80 80
07600540
57
62 92 80 80
08600630
74
83 121 125 125
gR
100 100
HSJ
08600860
92
104 165 160 160 150 150