240 Unidrive M702 User Guide
Issue Number: 3
Ensure cables used suit local wiring regulations.
Table 12-18 Cable ratings (200 V)
Table 12-19 Cable ratings (400 V)
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input Output Input Output
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
03200050
1.5
4
1.5
4
14
10
14
10
03200066
03200080
44
12 12
03200106
04200137
6
8
6
8
10
8
10
8
04200185
8
888
05200250
10
10 10 10 8 8 8 8
06200330
16
25
16
25
4
3
4
3
06200440
25
25 3 3
07200610
35
70
35
70
2
1/0
2
1/007200750 11
07200830
70
70 1/0 1/0
08201160
95
2 x 70
95
2 x 70
3/0
2 x 1
3/0
2 x 1
08201320 2 x 70 2 x 70 2 x 1 2 x 1
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input Output Input Output
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
03400025
1.5
4
1.5
4
18
10
18
10
03400031 16 16
03400045
14 1403400062
2.5 2.5
03400078
03400100 12 12
04400150
6
8
6
8
10
8
10
8
04400172
88
88
05400270
666 6
8888
05400300
06400350
10
25
10
25
6
3
6
306400420
16 16
44
06400470
25 25
33
07400660
35
70
35
70
1
1/0
1
1/007400770
50 50
22
07401000
70 70
1/0 1/0
08401340
2 x 50
2 x 70
2 x 50
2 x 70
2 x 1
2 x 1/0
2 x 1
2 x 1/0
08401570
2 x 70 2 x 70
2 x 1/0 2 x 1/0