2 CG Drives & Automation 01-7492-01r1
EMC Regulations
In order to comply with the EMC Directive, it is absolutely
necessary to follow the installation instructions. All
installation descriptions in this manual follow the EMC
Directive.
Mains voltage selection
The AC drive may be ordered for use with the mains voltage
range listed below.
VFX48: 230-480 V
VFX52: 440-525 V
VFX69: 500-690 V
Voltage tests (Megger)
Do not carry out voltage tests (Megger) on the motor, before
all the motor cables have been disconnected from the AC
drive.
Condensation
If the AC drive is moved from a cold (storage) room to a
room where it will be installed, condensation can occur.
This can result in sensitive components becoming damp. Do
not connect the mains voltage until all visible dampness has
evaporated.
Power factor capacitors for
improving cos
Ď•
Remove all capacitors from the motor and the motor outlet.
Precautions during Autoreset
When the automatic reset is active, the motor will restart
automatically provided that the cause of the trip has been
removed. If necessary take the appropriate precautions.
Transport
To avoid damage, keep the AC drive in its original
packaging during transport. This packaging is specially
designed to absorb shocks during transport.
IT Mains supply
The AC drives can be modified for an IT mains supply,
(non-earthed neutral), please contact your supplier for
details.
Alarms
Never disregard an alarm. Always check and remedy the
cause of an alarm.
Heat warning
DC-link residual voltage
HOT SURFACE!
Be aware of specific parts on the AC
drive having high temperature.
WARNING!
After switching off the mains supply,
dangerous voltage can still be present
in the AC drive. When opening the AC
drive for installing and/or
commissioning activities wait at least 7 minutes.
In case of malfunction a qualified technician
should check the DC-link or wait for one hour
before dismantling the AC drive for repair.