110 Functional description CG Drives & Automation 01-7492-01r1
11.2.6 Serial Communication [260]
The integrated RS485 interface on terminal X1: A+ and B-
will always be enabled regardless of setting in menu [261]
Comm type. Further, it may be used in parallel to any
Fieldbus option on X4 interface.
Menu [262] RS232/485 and its sub menus are used to
configure the integrated RS485 interface.
This function is to define the communication parameters for
serial communication. There are two types of options
available for serial communication, RS232/485 (Modbus/
RTU) and fieldbus modules (CANopen, Profibus,
DeviceNet, Modbus/TCP, Profinet IO, EtherCAT and
EtherNet/IP).
For more information see chapter 9. Communication page
75 and respective option manual.
Comm Type [261]
Select RS232/485 [262] or Fieldbus [263].
RS232/485 [262]
Press Enter to set up the parameters for RS-232/485
(Modbus/RTU) communication.
Baud rate [2621]
Set the baud rate for the communication.
Address [2622]
Enter the unit address for the AC drive.
Fieldbus [263]
Press Enter to set up the parameters for fieldbus
communication.
Address [2631]
Enter/view the unit/node address of the AC drive. Read and
write access for CANopen, Profibus, DeviceNet. Read - only
for EtherCAT.
261 Com Type
Default: RS232/485
RS232/485 0
Integrated RS485 interface enabled.
Fieldbus interface on X4 disabled
(RESET).
Fieldbus 1
Fieldbus selected (CANopen, Profibus,
DeviceNet, Modbus/TCP, Profinet IO,
EtherCAT or EtherNet/IP). Integrated
RS485 interface enabled (can be used in
parallel to fieldbus option).
NOTE: Toggling the setting in this menu will perform a
soft reset (re-boot) of the Fieldbus module.
262 RS232/485
NOTE: This address is only used for the integrated/
isolated RS485 option.
2621 Baudrate
Default: 9600
2400 0
Selected baud rate
4800 1
9600 2
19200 3
38400 4
57600 5
115200 6
NOTE: This address is only used for the integrated/
isolated RS485 option.
2622 Address
Default: 1
Selection: 1–247
263 Fieldbus
2631 Address
Default: 62
Range:
CANopen 1-127, Profibus 0–126,
DeviceNet 0–63
Node address valid for CANopen (RW), Profibus(RW),
DeviceNet (RW) and EtherCAT (RO).