EasyManuals Logo

Emotron VFX 2.1 User Manual

Emotron VFX 2.1
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
162 CG Drives & Automation 01-7492-01r1
Digital Out 2 [542]
Sets the function for the digital output 2.
11.5.5 Relays [550]
Submenu with all the settings for the relay outputs. The
relay mode selection makes it possible to establish a “fail
safe” relay operation by using the normal closed contact to
function as the normal open contact.
Relay 1 [551]
Sets the function for the relay output 1. Same function as
digital output 1 [541] can be selected.
Relay 2 [552]
Sets the function for the relay output 2.
Relay 3 [553]
Sets the function for the relay output 3.
Board Relay [554] to [55C]
These additional relays are only visible if an I/O option
board is fitted in slot 1, 2, or 3. The outputs are named B1
Relay 1–3, B2 Relay 1–3 and B3 Relay 1–3. B stands for
board and 1–3 is the number of the board which is related to
the position of the I/O option board on the option
mounting plate. See menu DigOut 1 [
541].
NOT6 96 NOT gate 6 output
NOT7 97 NOT gate 7 output
NOT8 98 NOT gate 8 output
CTR1 99 Counter 1 output
CTR2 100 Counter 2 output
CLK1 101 Clock logic 1output
CLK2 102 Clock logic 2 output
Enc Error 103 Tripped on Encoder error
Crane Comm 104 Crane Communication lost
Spin Start 105 Spin start is active
kWh-Pulses 106 kWh pulses counter
STO Active 107
STO is active.
The digital output reflects the signal
reported to the control board, while
the control board internally and PPU
ignore the STO during power up,
power down and standby.
ComFlt Set 109
Parameter set is changed in
accordance with menu [246] due to a
communication fault.
NOTE: The definitions described here are valid for the
active output condition.
542 DigOut2
Default: Brake
Selection: Same as in menu DigOut 1 [541].
NOTE: Additional relays will become available when I/
O option boards are connected. Maximum 3 boards
with 3 relays each.
551 Relay 1
Default: Trip
Selection: Same as in menu DigOut 1
[541].
NOTE: The definitions described here are valid for the
active output condition.
552 Relay 2
Default: Run
Selection: Same as in menu DigOut 1
[541].
553 Relay 3
Default: Off
Selection: Same as in menu DigOut 1 [541].
NOTE: Visible only if optional board is detected or if
any input/output is activated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VFX 2.1 and is the answer not in the manual?

Emotron VFX 2.1 Specifications

General IconGeneral
BrandEmotron
ModelVFX 2.1
CategoryDC Drives
LanguageEnglish

Related product manuals