Commissioning Proline Promass F 300 EtherNet/IP
106
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Select medium Select medium type. Liquid
Gas
Liquid
Select gas type The Gas option is selected in
the Select medium parameter.
Select measured gas type. Air
Ammonia NH3
Argon Ar
Sulfur hexafluoride
SF6
Oxygen O2
Ozone O3
Nitrogen oxide
NOx
Nitrogen N2
Nitrous oxide N2O
Methane CH4
Hydrogen H2
Helium He
Hydrogen chloride
HCl
Hydrogen sulfide
H2S
Ethylene C2H4
Carbon dioxide
CO2
Carbon monoxide
CO
Chlorine Cl2
Butane C4H10
Propane C3H8
Propylene C3H6
Ethane C2H6
Others
Methane CH4
Reference sound velocity In the Select gas type
parameter, the Others option
is selected.
Enter sound velocity of gas at
0 °C (32 °F).
1 to 99 999.9999 m/
s
415.0 m/s
Temperature coefficient sound
velocity
The Others option is selected
in the Select gas type
parameter.
Enter temperature coefficient
for the gas sound velocity.
Positive floating-
point number
0 (m/s)/K
Pressure compensation Select pressure compensation
type.
Off
Fixed value
External value
Current input 1
*
Current input 2
*
Off
Pressure value The Fixed value option is
selected in the Pressure
compensation parameter.
Enter process pressure to be
used for pressure correction.
Positive floating-
point number
0 bar
External pressure The External value option is
selected in the Pressure
compensation parameter.
Shows the external process
pressure value.
Positive floating-
point number
0 bar
* Visibility depends on order options or device settings