Proline Promass F 300 EtherNet/IP Diagnostics and troubleshooting
187
Error Possible causes Solution
Operation with FieldCare or
DeviceCare via CDI-RJ45 service
interface (port 8000)
Firewall of computer or network is
preventing communication
Depending on the settings of the
firewall used on the computer or in
the network, the firewall must be
adapted or disabled to allow
FieldCare/DeviceCare access.
Flashing of firmware with FieldCare
or DeviceCare via CDI-RJ45 service
interface (via port 8000 or TFTP
ports)
Firewall of computer or network is
preventing communication
Depending on the settings of the
firewall used on the computer or in
the network, the firewall must be
adapted or disabled to allow
FieldCare/DeviceCare access.
12.2 Diagnostic information via light emitting diodes
12.2.1 Transmitter
Different LEDs in the transmitter provide information on the device status.
1 2 3 4
5
A0029629
1 Supply voltage
2 Device status
3 network status
4 Port 1 active: EtherNet/IP
5 Port 2 active: EtherNet/IP and service interface (CDI)
LED Color Meaning
1 Supply voltage Off Supply voltage is off or too low.
Green Supply voltage is ok.
2 Device status/module
status
Off Firmware error.
Green Device status is ok.
Flashing green Device is not configured.
Flashing red A diagnostic event with "Warning" diagnostic
behavior has occurred.
Red A diagnostic event with "Alarm" diagnostic behavior
has occurred.
Flashing red/green The device restarts/self-test.
3 Network status Off The device does not have an EtherNet/IP address.
Green EtherNet/IP connection is active.
Flashing green The device has an Ethernet/IP address but no
EtherNet/IP connection is active.