Commissioning Proline Promass F 300 EtherNet/IP
140
10.5.13 Configuring the partial filled pipe detection
The Partial filled pipe detection wizard guides you systematically through all parameters
that have to be set for configuring the monitoring of the pipe filling.
Navigation
"Setup" menu → Partially filled pipe detection
Partially filled pipe detection
Assign process variable
→  140
Low value partial filled pipe detection
→  140
High value partial filled pipe detection
→  140
Response time part. filled pipe detect.
→  140
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign process variable Select process variable for
partially filled pipe detection.
Off
Density
Reference density
Off
Low value partial filled pipe
detection
One of the following options is
selected in the Assign process
variable parameter
(→  140):
Density
Reference density
Enter lower limit value for
deactivating partialy filled pipe
detection.
Signed floating-point
number
200
High value partial filled pipe
detection
One of the following options is
selected in the Assign process
variable parameter
(→  140):
Density
Reference density
Enter upper limit value for
deactivating partialy filled pipe
detection.
Signed floating-point
number
6 000
Response time part. filled pipe
detect.
One of the following options is
selected in the Assign process
variable parameter
(→  140):
Density
Reference density
Enter time before diagnostic
message is displayed for
partially filled pipe detection.
0 to 100 s 1 s