EasyManua.ls Logo

Endress+Hauser Proline Promass F 300 - Hardware Settings

Endress+Hauser Proline Promass F 300
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Proline Promass F 300 EtherNet/IP Electrical connection
47
Status input
1
2
3
A0028764
 15 Connection example for status input
1 Automation system with status output (e.g. PLC)
2 Power supply
3 Transmitter: Observe input values
7.5 Hardware settings
7.5.1 Setting the device address
The IP address of the measuring device can be configured for the network via DIP switches.
Addressing data
IP address and configuration options
1st octet 2nd octet 3rd octet 4th octet
192. 168. 1. XXX
Can only be configured via software addressing Can be configured via software addressing
and hardware addressing
IP address range 1 to 254 (4th octet)
IP address broadcast 255
Addressing mode ex
works
Software addressing; all DIP switches for hardware addressing are set to OFF.
IP address ex works DHCP server active
Software addressing: The IP address is entered via the IP address parameter
(→  104) .
Setting the IP address
Risk of electric shock when opening the transmitter housing.
Before opening the transmitter housing:
Disconnect the device from the power supply.
The default IP address may not be activated →  48.

Table of Contents

Related product manuals