Proline Promass F 300 EtherNet/IP Commissioning
143
Linear expansion coefficient
→ 143
Square expansion coefficient
→ 143
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Corrected volume flow calculation – Select reference density for
calculating the corrected
volume flow.
• Fixed reference
density
• Calculated
reference density
• External reference
density
• Current input 1
*
• Current input 2
*
Calculated reference
density
External reference density In the Corrected volume flow
calculation parameter, the
External reference density
option is selected.
Shows external reference
density.
Floating point
number with sign
–
Fixed reference density The Fixed reference density
option is selected in the
Corrected volume flow
calculation parameter
parameter.
Enter fixed value for reference
density.
Positive floating-
point number
1 kg/Nl
Reference temperature The Calculated reference
density option is selected in
the Corrected volume flow
calculation parameter.
Enter reference temperature
for calculating the reference
density.
–273.15 to 99 999 °C Country-specific:
• +20 °C
• +68 °F
Linear expansion coefficient The Calculated reference
density option is selected in
the Corrected volume flow
calculation parameter
parameter.
Enter linear, medium-specific
expansion coefficient for
calculating the reference
density.
Signed floating-point
number
0.0 1/K
Square expansion coefficient The Calculated reference
density option is selected in
the Corrected volume flow
calculation parameter
parameter.
For media with a non-linear
expansion pattern: enter the
quadratic, medium-specific
expansion coefficient for
calculating the reference
density.
Signed floating-point
number
0.0 1/K²
* Visibility depends on order options or device settings
10.6.3 Carrying out a sensor adjustment
The Sensor adjustment submenu contains parameters that pertain to the functionality of
the sensor.