System integration Proline Promass F 300 EtherNet/IP
82
9.4.2 Input and output groups
Possible configurations
Configuration 1: Exclusive Owner Multicast
Input Assembly Fix Instance Size (byte) Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 64 398
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 2: Input Only Multicast
Input Assembly Fix Instance Size (byte) Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398
Output Assembly Fix O → T Configuration 0 x C7
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 3: Exclusive Owner Multicast
Input Assembly Configurable Instance Size (byte) Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 65 88 5
Configuration 4: Input Only Multicast
Input Assembly Configurable Instance Size (byte) Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398
Output Assembly Fix O → T Configuration 0 x C7
Input Assembly Fix T → O Configuration 0 x 64 88 5
Configuration 5: Exclusive Owner Multicast
Input Assembly Fix Instance Size (byte) Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 69
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 6: Input Only Multicast
Input Assembly Fix Instance Size (byte) Min. RPI (ms)
Input Assembly Configurable Configuration 0 x 69
Output Assembly Fix O → T Configuration 0 x C7
Input Assembly Fix T → O Configuration 0 x 65 44 5