Diagnostics and troubleshooting Proline Promass F 300 EtherNet/IP
192
12.4 Diagnostic information in the Web browser
12.4.1 Diagnostic options
Any faults detected by the measuring device are displayed in the Web browser on the
home page once the user has logged on.
2 3
1
A0031056
1 Status area with status signal
2 Diagnostic information →  190
3 Remedy information with Service ID
In addition, diagnostic events which have occurred can be shown in the Diagnostics
menu:
Via parameter
Via submenu →  210
Status signals
The status signals provide information on the state and reliability of the device by
categorizing the cause of the diagnostic information (diagnostic event).
Symbol Meaning
Failure
A device error has occurred. The measured value is no longer valid.
Function check
The device is in service mode (e.g. during a simulation).
Out of specification
The device is operated:
Outside its technical specification limits (e.g. outside the process temperature range)
Maintenance required
Maintenance is required. The measured value is still valid.
The status signals are categorized in accordance with VDI/VDE 2650 and NAMUR
Recommendation NE 107.