Proline Promass F 300 EtherNet/IP Technical data
231
Configuration of the device
address
• DIP switches on the electronics module for IP addressing (last octet)
• DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)
Device Level Ring (DLR) Yes
System integration Information regarding system integration → 80.
• Cyclic data transmission
• Block model
• Input and output groups
16.5 Power supply
Terminal assignment → 36
Device plugs available → 36
Pin assignment, device plug → 36
Supply voltage
Order code for
"Power supply"
terminal voltage Frequency range
Option D DC24 V ±20% –
Option E AC100 to 240 V –15…+10% 50/60 Hz
Option I
DC24 V ±20% –
AC100 to 240 V –15…+10% 50/60 Hz
Power consumption Transmitter
Max. 10 W (active power)
Current consumption Transmitter
• Max. 400 mA (24 V)
• Max. 200 mA (110 V, 50/60 Hz; 230 V, 50/60 Hz)
Power supply failure • Totalizers stop at the last value measured.
• Configuration is retained in the plug-in memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Electrical connection → 37
Potential equalization → 43