Commissioning Proline Promass F 300 EtherNet/IP
124
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Assign limit The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Select process variable for limit
function.
Mass flow
Volume flow
Corrected volume
flow
Target mass flow
*
Carrier mass flow
*
Target volume
flow
Carrier volume
flow
Target corrected
volume flow
Carrier corrected
volume flow
Density
Reference density
Reference density
alternative
GSV flow
GSV flow
alternative
NSV flow
NSV flow
alternative
S&W volume flow
Water cut
Oil density
Water density
Oil mass flow
Water mass flow
Oil volume flow
Water volume flow
Oil corrected
volume flow
Water corrected
volume flow
Concentration
*
Temperature
Totalizer 1
Totalizer 2
Totalizer 3
Oscillation
damping
Pressure
Mass flow
Assign flow direction check The Switch option is
selected in the Operating
mode parameter.
The Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
Off
Volume flow
Mass flow
Corrected volume
flow
Mass flow
Assign status The Switch option is
selected in the Operating
mode parameter.
The Status option is
selected in the Switch
output function parameter.
Select device status for switch
output.
Partially filled pipe
detection
Low flow cut off
Partially filled pipe
detection

Table of Contents