10 Technical data PROline Prosonic Flow 93 PROFIBUS-DP/-PA
144 Endress+Hauser
10.1.3 Input
Measured variable Flow velocity
(transit time difference proportional to flow velocity)
Measuring range Typically v = 0...15 m/s with the specified measuring accuracy for Prosonic Flow W/P
Typically v = 0...10 m/s with the specified measuring accuracy for Prosonic Flow U
Operable flow range Over 150 : 1
10.1.4 PROFIBUS output variables
Output signal PROFIBUS-DP/-PA interface:
PROFIBUS-DP/PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP),
Profile Version 3.0, galvanically isolated
Signal on alarm PROFIBUS-DP/-PA interface:
Status and alarm messages in accordance with PROFIBUS-PA Profile Version 3.0.
Current consumption 11 mA
Permissible feed voltage 9...32 V, not intrinsically safe
FDE (Fault Disconnection
Electronic)
0 mA
Data transmission rate PROFIBUS-PA: supported baud rate = 31.25 kBaud
PROFIBUS-DP: supported baud rate = 9.6 kBaud...12 MBaud
Signal coding PROFIBUS-PA: Manchester II
PROFIBUS-DP: NRZ code

Table of Contents

Other manuals for Endress+Hauser Proline Prosonic Flow 93

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Proline Prosonic Flow 93 and is the answer not in the manual?

Endress+Hauser Proline Prosonic Flow 93 Specifications

General IconGeneral
BrandEndress+Hauser
ModelProline Prosonic Flow 93
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals