PROline Prosonic Flow 93 PROFIBUS-DP/-PA 6 Commissioning
Endress+Hauser 85
6.2.3 Commissioning with local display
!
Note!
You must enter a numerical code (factory setting: 93) before altering device functions,
numerical values or factory settings
Page 60.
The following steps have to be carried out one after the other:
1. Check the hardware write protection:
BASIC FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA)
CONFIGURATION (610)
WRITE PROTECT (write protection, 6102)
2. Enter the tag name:
BASIC FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA)
CONFIGURATION (610)
TAG NAME (6100)
3. Assign a bus address if this has not already been effected via the corresponding
miniature switches (see Page 79):
BASIC FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA)
CONFIGURATION (610)
BUS ADDRESS (6101)
4. Select the system unit:
Via the “System unit” group: MEASURED VARIABLES (A)
SYSTEM UNITS
(ACA)
CONFIGURATION (040) UNIT VOLUME FLOW (0402) UNIT
VOLUME (0403)
The system unit set becomes effective in the automation system once the SET
UNIT TO BUS function has been activated: BASIC FUNCTION (G)
PROFIBUSHDP/-PA (GBA/GCA)
OPERATION (614) SET UNIT TO BUS
(6141)
! Note!
Engineering units for the totalizers must be configured separately as explained in
Point 5.
The measured values are transmitted in the system units - as described on
Page 99 ff. - to the automation system via the cyclic data exchange. If the system
unit of a measured value is changed using the local display, this will not have an
immediate effect on the output of the Analog Input Block and therefore will not
influence the measured value which is transmitted to the automation system.
The altered system unit of the measured value will only be transmitted to the
automation system once the “SET UNIT TO BUS“ function in the block BASIC
FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA) OPERATION (614) 
SET UNIT TO BUS (6141) has been activated.
5. Configuring totalizers 1–3:
Prosonic Flow 93 has 3 totalizers. The following description provides an example
for totalizer 1.
Select the process variable, e.g. VOLUME FLOW CH1: BASIC FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA)
 TOTALIZER (613)  CHANNEL (channel,
6133)
Enter the required totalizer units:
BASIC FUNCTION (G)
 PROFIBUS-DP/-PA (GBA/GCA)  TOTALIZER
(613)
UNIT TOTALIZER (6134)
Configure totalizer status, e.g. for totalizing:
BASIC FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA)  TOTALIZER
(613)
SET TOTALIZER (6135)
Configure totalizer mode, e.g. for balancing:
BASIC FUNCTION (G)
 PROFIBUS-DP/-PA (GBA/GCA) TOTALIZER
(613)
 TOTALIZER MODE (6137)
6. Select the GSD file:
BASIC FUNCTION (G)
PROFIBUS-DP/-PA (GBA/GCA) OPERATION (614)
 SELECT GSD (6140)