EasyManua.ls Logo

Enertech AV Series - Antifreeze Percentages by Volume Table; Antifreeze Specific Gravity Table

Enertech AV Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enertech Global, LLC 35
AV : MD/ME - Rev. A Models
Installaon and Operaons Manual

Type of Anfreeze
Minimum Temperature for Freeze Protecon
10°F (-12.2°C) 15°F (-9.4°C) 20°F (-6.7°C) 25°F (-3.9°C)
Propylene Glycol 30% 25% *20% *13%
Methanol 21% 17% 13% 5%
Ethanol 26% 23% 18% 13%
Heat Transfer Fluid (HTF) Mix according to manufacturer’s direcons on container label
Note: Anfreeze soluons are shown in pure form - not premixed
HTF is a premixed Methanol Soluon
*Concentraons below 25-30% (consult manufacturer) typically require addional inhibitors.
0.9600
0.9700
0.9800
0.9900
1.0000
1.0100
1.0200
1.0300
1.0400
1.0500
0 5 10 15 20 25 30
Ethanol Methanol Propylene Glycol
Freeze Protection, deg F
Specific Gravity
Pure water has a specific gravity of 1
Glycols are heavier than water (>1)
Alcohols are lighter than water (<1)

Notes:
1. Consult with your representave or distributor if you have any quesons regarding anfreeze selecon or use.
2. Some anfreeze suppliers and manufacturers recommend the use of either de-ionized or dislled water with their
products. Some brands are designed to work with tap water. Consult the anfreeze manufacturer’s technical data.
Secon 6: Anfreeze

Table of Contents

Related product manuals