EasyManua.ls Logo

Enertech AV Series - Section 7: Field Wiring; Introduction; Communication

Enertech AV Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enertech Global, LLC 37
AV : MD/ME - Rev. A Models
Installaon and Operaons Manual
Optional connections
Communication
F2120 communicates with NIBE indoor modules/contr ol
modules by connecting a three core, screened cable (max
area 0.75 mm²) to terminal block X22:1– 4, as shown in
the following image.
For cascade connection, join terminal block X23 with
X22 to the next heat pump .
Softwar e version
In order for F2120 to be able to communicate with in-
door module (VVM ) / contr ol module (SMO ) the softwar e
version must be according to the table.
Softw ar e versionIndoor module /
Contr ol module
v7568R4VVM 310 / VVM 500
v7530R5VVM 320 / VVM 325
v7607R3SMO 20
v7635R5SMO 40
Disconnect the connections in F2120
PRESS
1
PULL
LEK
2
3
Pull up!
Push down!
1 2 3
29Chapter 5 | Electrical connectionsNIBE F2120

EAV does not include a circuit breaker on the incoming
power supply. The heat pump’s supply cable must be
connected to a circuit breaker. A disconnect must be
installed near the unit per local code requirements.
The roung of cables for heavy current and signals should
be made out through the cable openings on the heat
pump’s right-hand side, seen from the front.
The communicaon cable must be a shielded cable and
be connected between EAV terminal block X22 and the
indoor module/control module
Connect the ushing pump to the indoor module/control
module.
Note: Electrical installaon and wiring must be carried out in
accordance with local code by a qualied technician.

A power block is provided for incoming power to the EME/
EMD. This circuit supplies power to all of the controls, internal
pump, and immersion heater (if equipped).
Note: Reference the electrical data for circuit sizing.
Low Voltage
The EME/EMD eld wiring provides dry contact inputs to
interface directly with industry standard zone controllers and
aquastats. These are indicated with the following input pairs:
Heat: Radiant heang demand input
HHeat: Air handler heang demand input (120°F outlet
temperature)
Cool: Air handler cooling demand input (low temperature
water)
DHW: Domesc hot water thermistor (connect to thermistor
that is pre-installed in Turbomax tank)
OAT and OAT: These Terminals are Not Used, The outdoor
sensor is located in the Outdoor Unit, BT28 Sensor.
Secon 7: Field Wiring

EAV communicates with Enertech indoor modules/control
modules by connecng a 3-conductor, shielded cable (max
area 0.75 mm²) to terminal block X22:1–4, as shown in the
following images.

Line Voltage

24
Enertech Global
AV/EM Models IOM
NOTE: USE THE UNINSULATED
CONDUCTOR FOR THIS CONNECTION.
Outdoor Unit Control Board
NOTE: USE THE 2 INSULATED
CONDUCTORS FOR A & B
Communica ons Wiring Between
Indoor and Outdoor Units
NOTE:
USE THE UNINSULATED
CONDUCTOR FOR GND
CONNECTION
24
Enertech Global
AV/EM Models IOM
NOTE: USE THE UNINSULATED
CONDUCTOR FOR THIS CONNECTION.
Outdoor Unit Control Board
NOTE: USE THE 2 INSULATED
CONDUCTORS FOR A & B
Communica ons Wiring Between
Indoor and Outdoor Units
NOTE:
USE THE UNINSULATED
CONDUCTOR FOR GND
CONNECTION

Table of Contents

Related product manuals