Enertech Global, LLC 43
AV : MD/ME - Rev. A Models
Installaon and Operaons Manual
Idle
The system is o and waing for a call.
Pump Start
The load pump runs at maximum speed and the EEV
(Electronic Expansion Valve) opens completely to equalize the
system and prepare for the compressor to start. The diverng
valve and reversing valve move into posion accordingly.
The reversing valve is energized only in cooling.
The diverng valve is energized only in hot water heang.
This state runs for one minute to allow temperatures and
pressures to equalize and provide relevant sensor informaon.
This step is primarily a vericaon of condions.
If the pressures have not equalized, the system will not
connue to the running phase. Also, the system will verify that
the load temperature does not exceed the required target
temperature (see the next secon “Variable Speed Control”).
Compressor Start
The EEV moves to the starng posion and the compressor
starts at 2700 RPM (minimum speed 1650 RPM).
Run
The compressor modulates speed according to the required
load. The EEV modulates as needed to maintain 8°F superheat.
The pump modulates to maintain ΔT across the heat
exchangers. See the next secon, “Variable Speed Control”,
for more informaon.
Compressor Stop
Aer all calls have been sased, the compressor ramps down
gradually to zero RPM.
Pump Stop
The pump maintains its current speed for one minute as it
slowly ramps down to turn o.
Note: Zone controls must allow post purge aer a call to allow
the internal load pump to stop.
ASC
The an-short cycle mer prevents the compressor from
running for three minutes aer the unit has been shut down.
All calls will be held unl the ASC mer has expired. The three
minute ASC is in addion to the pump start and stop duraons
to provide an industry standard ve minute an-shortcycle of
the compressor.
• The compressor ramps down to the minimum speed, in
correlaon to the operang envelope, for 30-60 seconds.
The pump will slow down as compressor capacity ramps
down.
• The reversing valve is energized or de-energized if
switching from heang to cooling or cooling to heang. If
the system is switching from heang to hot water or hot
water to heang, the reversing valve does not change.
• The zone valves in the Indoor Module switch from the
hydronic load to the domesc hot water tank or the zone
valves switch from DHW to hydronic heang/cooling.
• Aer the valves have transioned, the system resumes to
its normal running mode where the pump, compressor,
and EEV modulate accordingly. Note that when switching
from DHW to cooling or cooling to DHW, the valves will
not switch to hydronic load or DHW tank if the leaving
load temperature is not within 20°F of the target
temperature. This approach eliminates hot water going
to a fan coil in cooling mode or chilled water going to the
DHW tank.
When the higher priority call is sased, and there is sll a call
holding, the system will transion back to the original call in
the same manner. The compressor is able to connue running
and thus no ASC delay is experienced.
Variable Speed Control
The use of the variable speed compressor and pump includes
advanced control algorithms to match the load demand of
the space. The control described here takes place during the
“Run” poron in the system sequence of operaon described
in the previous secon.
Compressor
Control of the compressor is based on the target temperature
of the system. The system monitors the current load out
temperature and compares to the target temperature. Using
the control algorithm, the system seeks to maintain the exact
target temperature. Outlet temperature above or below
the target temperature causes the compressor to throle
faster or slower as needed. In radiant oor heang, with an
outdoor thermistor, the outdoor reset dictates the targeted
load temperature. In cooling and hot water, the stac menu
sengs control the target temperature.
This control allows the system to react to changing condions.
As zone valves open and close, the compressor speed is
adjusted to meet the current demand.
In some small load situaons, such as very small radiant
zones, the system may not be able to run slow enough to
avoid thermal runaway. To accommodate this situaon, the
compressor can shut down when the load outlet temperature
over/under shoots its target by 3°F. During this me, the
pump will connue to circulate and the So Idle mer is
started.
The compressor will be cycled on again when the So Idle
mer expires AND the outlet temperature has dropped below
the target temperature. All priories are sll obeyed during
this me. If the call becomes sased the system will shut
down normally.
Note: It is recommended to size zones in order to avoid this
cycling condion. It is preferred to avoid compressor cycling
and improve eciency.
Pump
When the pump is in “auto” mode, it controls to maintain
ΔT (Default 5°F) across the heat exchangers. To do so, load
entering and leaving temperatures are connually monitored.
A sensed ΔT above the 5°F setpoint will cause the pump to run
faster. Below the setpoint causes the pump to run slower –
down to the set minimum speed.
Note: If, aer setup, the EME/EMD detects the minimum
ow rate of less than 5.0 GPM, it will aempt to increase the
minimum ow percentage unl 5.0 GPM is achieved.
Secon 8: Controls