MACHINE PARAMETERS
6.
SOFT: V02.2X
·281·
PLC Parameters
OANALOG1 (P111) OANALOG2 (P114) OANALOG3 (P117)
OANALOG4 (P120)
They are used to set the remote modules.
They indicate the number of analog outputs of each of the 4 remote modules; a CAN node number
identifies each one in the system. Its value will be 4 if it is a Fagor remote module.
PT100_1 (P112) PT100_2 (P115) PT100_3 (P118)
PT100_4 (P121)
They are used to set the remote modules.
They indicate the number of physical connections available for PT100 probes in each of the 4 remote
modules and also indicate which ones are connected. All this information is reflected in a 16-bit
string. Their value will be 0000 0000 0000 0011 if it is a Fagor remote module (2 physical
connections, bits 0 and 1 set to "1") and whether they are both connected (bits 4 and 5 set to "0")
or not. See table below.
A remote module may have physical connections for PT100 probes, but they are not connected.
That is why there is a bit indicating that there is a physical connection for the PT100 probe and
another bit to indicated whether a probe is connected or not.
Therefore, for a 16-bit string:
If the probe is not properly connected or the cable is defective, the CNC will display an error message
that will be treated like the errors at the digital inputs/outputs.
NUIANA1 (P122) NUIANA2 (P124) NUIANA3 (P126)
NUIANA4 (P128)
They are used to set the remote modules.
They indicate the number of the first analog input of each remote module. The rest of analog inputs
of the same module will be numbered sequentially.
NUOANA1 (P123) NUOANA2 (P125) NUOANA3 (P127)
NUOANA4 (P129)
They are used to set the remote modules.
They indicate the number of the first analog output of each remote module. The rest of analog outputs
of the same module will be numbered sequentially.
If the value of all these parameters is zero (they are by default), the numbering of the analog
inputs/outputs will be consecutive to the last local inputs/outputs.
Their maximum value will be 16, both for the analog inputs and analog outputs.
On power-up, the CNC verifies that the number of analog inputs/outputs detected at the module
matches the value assigned to the relevant machine parameters.
If these values do not match, the CNC screen will display a message indicating it and then it will
turn the remote module off.
PT100_1 = x x x x x x x x xx 0/1 0/1 xx 0/1 0/1
bit 0 Does it have a physical connection for PT100_1 probe? no / yes 0/1
bit 1 Does it have a physical connection for PT100_2 probe? no / yes 0/1
bit 4 Is there a PT100_1 probe connected to it? yes / no 0/1
bit 5 Is there a PT100_2 probe connected to it? yes / no 0/1
... others Reserved
for Fagor remote modules
bit
15 ....... 012312 11 ....... 8 7 ........ 4