OPERATION MT100 Multipoint Flow Meter
Command 44: Write Primary Variable Units
No Command-Specific Errors
Note: 1. The value returned in the response data bytes reflects the value actually used by the device.
Command 45: Trim DAC Zero – Measured Current Chan #1 (in mA)
Ext. Measured Current Ch. #1 Level (mA units)
Actual Measured Current Ch. #1 Level (mA units)
No Command-Specific Errors
Passed Parameter Too Large
Passed Parameter Too Small
Incorrect Loop Current Mode or Value
Loop Current Not Active (Device in Multidrop mode)
Note: 1. The value returned in the response data bytes reflects the rounded or truncated value actually used by the
device.
Command 46: Trim DAC Gain – Measured Current Chan #1 (in mA)
Ext. Measured Current Ch. #1 Level (mA units)
Actual Measured Current Ch. #1 Level (mA units)
No Command-Specific Errors
Passed Parameter Too Large
Passed Parameter Too Small
Incorrect Loop Current Mode or Value
Loop Current Not Active (Device in Multidrop mode)
Note: 1. The value returned in the response data bytes reflects the rounded or truncated value actually used by the device.
Fluid Components International LLC 56