B Diagnostic messages
82 Festo – GDCP-CMMP-M0-HW-EN – 1511c – English
B.2 Diagnostic messages with instructions for fault clearance
Error group 0 Information
No. Code Message Reaction
0-0 - Invalid error Ignore
Cause Information: An invalid error entry (corrupted) was found in the
diagnostic memory marked with this error number.
The system time entry is set to 0.
Action –
0-1 - Invalid error detected and corrected Ignore
Cause Information: An invalid error entry (corrupted) was found in the
diagnostic memory and corrected. The additional information con
tains the original error number.
The system time entry includes the address of the corrupted error
number.
Action –
0-2 - Error cleared Ignore
Cause Information: Active errors were acknowledged.
Action –
0-7 - Subsequent entry Ignore
Cause Information: è Diagnostic memory entry.
Action –
0-8 - Controller switched on Ignore
Cause Information: è Diagnostic memory entry.
Action –
0-22 - Default parameter record loaded Ignore
Cause Information: è Diagnostic memory entry.
Action –
Error group 1 Stack overflow
No. Code Message Reaction
1-0 6180h Stack overflow PSoff
Cause – Incorrect firmware?
– Sporadic high processor load due to cycle time being too short
and specific processor-intensive processes (save parameter set
etc.).
Action Load an approved firmware.
Reduce the processor load.
Contact Technical Support.