A. Specifications and index
A-3
Festo Festo P .BE CP FB13-E-EN en 9910c
A.1 Technical specifications Field bus node CP FB13-E
General
Temperature range:
– operation
– storage/transport
-5°C ... + 50 °C
-20 °C ... + 70 °C
Relative humidity 95 %, non-condensing
Protection class as per EN 60529 529 Plug con-
nector inserted or provided with protective cap
IP 65
Protection against electric shock
Protection against direct and indirect contact as
per EN 60204-1/IEC 204
by means of PELV power units
(Protected Extra-Low Voltage)
Operating voltage for the electronics and the input modules
Pin 1
Operating voltage connection
– Rated value
– Tolerance:
24 V DC,
20.4 .. 26.4 V
Current consumption
– Pin 1 node FB13-E
– Complete electronics of the CP system
250 mA
see manual “CP system”, Table of current con-
sumption
Residual ripple 4 Vpp (within tolerance)
Bridging time during drop in logic voltage 20 ms