EasyManua.ls Logo

Fike FCP-75 - Page 113

Fike FCP-75
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Receivers Compatible with the Control Panel Reporting
FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021 113
Ground fault condition trouble YP Exp. ID YPNNXX0000 1 310 Exp. ID 000
Ground fault condition trouble restore YQ Exp. ID YQNNXX0000 3 310 Exp. ID 000
Initial power up RR 0 RRNN000000 1 305 00 000
Local programming aborted or ended with er-
rors
LU 0 LUNN000000 1 628 00 000
Local programming begin LB 0 LBNN000000 1 627 00 000
Local programming ended normally LS 0 LSNN000000 1 628 00 000
Network node trouble (panel missing) EM Panel ID EMNNNN0000 1 334 Panel ID 000
Network node trouble restore
(panel no longer missing)
EN Panel ID ENNNNN0000 3 334 Panel ID 000
OPG Inhibit Trouble FT Group # + 1000 FTNN001GGG 1 320 00 Group #
OPG Inhibit Trouble Restore FJ Group # + 1000 FJNN001GGG 3 320 00 Group #
OPG Inhibit of Releasing Group SS Group # + 1000 SSNN001GGG 1 203 00 Group #
OPG Inhibit of Releasing Group Restore SR Group # + 1000 SRNN001GGG 3 203 00 Group #
Phone line 1 trouble detected LT 1 LTNN000001 1 351 00 000
Phone line 1 trouble restore LR 1 LRNN000001 3 351 00 000
Phone line 2 trouble detected LT 2 LTNN000002 1 352 00 000
Phone line 2 trouble restore LR 2 LRNN000002 3 352 00 000
Printer is off-line trouble VZ Exp. ID VZNNXX0000 1 336 Exp. ID 000
Printer is off-line trouble restore VY Exp. ID VYNNXX0000 3 336 Exp. ID 000
Printer is out of paper trouble VO Exp. ID VONNXX0000 1 335 Exp. ID 000
Printer is out of paper trouble restore VI Exp. ID VINNXX0000 3 335 Exp. ID 000
Releasing Notif/Control Circuit Disabled pi Exp. ID SS Point # SSNNXXPPPP 1 203 Exp. ID Point #
Releasing Notif/Control Circuit enabled pi Exp. ID SR Point # SRNNXXPPPP 3 203 Exp. ID Point #
Remote programming aborted or ended with
errors
RU 0 RUNN000000 1 413 00 000
Remote programming ended normally RS 0 RSNN000000 1 412 00 000
Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103
Repeater ground fault trouble restore EN 0103 ENNN000103 3 334 Panel ID 103
Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100
Repeater missing trouble restore EN 0100 ENNN000100 3 334 Panel ID 100
Repeater Rx1 communication trouble EM 0101 EMNN000101 1 334 Panel ID 101
Repeater Rx1 communication trouble restore EN 0101 ENNN000101 3 334 Panel ID 101
Repeater Rx2 communication trouble EM 0102 EMNN000102 1 334 Panel ID 102
Repeater Rx2 communication trouble restore EN 0102 ENNN000102 3 334 Panel ID 102
SBUS Class A supervision lost ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS Class A supervision restore ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
SBUS expander trouble ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS expander trouble restore ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
SLC class A supervision trouble ET Exp. ID ETNNXX0000 1 331 Exp. ID 000
SLC class A supervision trouble restore ER Exp. ID ERNNXX0000 3 331 Exp. ID 000
SLC programming ended, system active TE 0 TENN000000 3 607 00 000
SLC programming started, system shut down TS 0 TSNN000000 1 607 00 000
SLC short circuit trouble ET Exp. ID ETNNXX0000 1 332 Exp. ID 000
SLC short circuit trouble restore ER Exp. ID ERNNXX0000 3 332 Exp. ID 000
Time changed event JT 0 JTNN000000 1 625 00 000
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module ID
# (If Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.2 Reporting Formats Table (Continued)

Table of Contents

Related product manuals