EasyManua.ls Logo

Fike FCP-75 - Page 117

Fike FCP-75
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Receivers Compatible with the Control Panel Reporting
FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021 117
ECS Control Circuit Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Control Circuit Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Relay Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Relay Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Notification Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Notification Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
External Reset/Silence/Fire Drill switch dis-
abled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
External Reset/Silence/Fire Drill switch en-
abled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
External Reset/Silence/Fire Drill switch trou-
ble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
External Reset/Silence/Fire Drill switch trou-
ble restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Interlock switch alarm (Water Release Zone) pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Interlock switch alarm restore (Water Release
Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Interlock switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Interlock switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Interlock switch trouble (Water Release
Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Interlock switch trouble restore (Water Re-
lease Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
LOC Mic Activated ECS Alarm pi Exp. ID QA 0 QANNXX0000 1 220 Exp. ID 000
LOC Mic Activated ECS Alarm Restore pi Exp. ID QH 0 QHNNXX0000 3 220 Exp. ID 000
LOC ECS # Alarm pi Exp. ID QA Emergency # QANNXXE000 1 220 +
Emer-
gency #
Exp. ID 000
LOC ECS # Alarm Restore pi Exp. ID QH Emergency # QHNNXXE000 3 220 +
Emer-
gency #
Exp. ID 000
Manual pull switch alarm pi Exp. ID FA Point # FANNXXPPPP 1 115 Exp. ID Point #
Manual pull switch alarm restore pi Exp. ID FH Point # FHNNXXPPPP 3 115 Exp. ID Point #
Manual pull switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Manual pull switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Manual pull switch trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Manual pull switch trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Manual release switch alarm
(Water Release Zone)
pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Manual release switch alarm restore (Water
Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Manual release switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Manual release switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Manual release switch trouble
(Water Release Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Manual release switch trouble restore (Water
Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Notification output point disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module ID
# (If Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.2 Reporting Formats Table (Continued)

Table of Contents