Programming Menu Quick Reference Programming Overview
FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021 83
1. Available on Internal SLC.
3. Available with SLC Family as IDP
4. Requires wireless gateway.
6. AUX SYNC setting is only applicable for the B200S/IV Sounder Base.
System
Options
con’t
Time Options
Water Flow Delay 0 - 90 Seconds *1 sec
Water Flow delay is
the number of
seconds before a
water flow alarm is
generated.
Section 9.6.2
Alarm Verify 60 to 250 seconds *60 sec
Low AC Report Time 0 - 30 hours *3 hrs
AC Freq:
50 Hz
*60Hz60 Hz
Internal
Clock Display Format
AM/PM
*AM/PM
MIL
Auto-resound
4 hours
*24 hours
24 hours
Miscellaneous
Options
SYNC Strobes when
Silenced
Y
*N
Section 9.6.5
N
Auto Display Events
Y
*N
N
Daylight Saving
Options
Auto Daylight Saving
Time
Y
*Y
Section 9.6.6
N
DST Start
Select week: 1st, 2nd, 3rd, 4th or
Last
Select month
DST End
Edit Banner Refer to Appendix B Section 9.6.7
SLC Family IDP Section 9.6.8
Jump
Start
AutoPrg
Y (Yes)
N (No)
Section 9.7
Restore
Defaults
Y (Yes)
N (No)
Section 9.8
*Default
Menu Options/Defaults Comments
Table 8.3 Programming Quick Reference List (Continued)