Maintainence
30.10.12 Kapitel/Chapter 7: Maintainence - Seite/Page 113
Fig. 7.9-2: Air filter mattReplace the Air filter matt
Close the Air filter housing.
7.10 Trouble shooting
GENERATOR OUTPUT VOLTAGE TOO LOW
If the generator delivers less than 24V current ("undervoltage"), there can be various reasons for this:
Cause Solution
PGMi is overloaded. Reduce the electrical load. (Switch off load)
Motor is not reaching the rated rpm. Refer to "motor faults" section.
MOTOR DOES NOT TURN OVER WHEN STARTING
Cause Solution
Battery main switch is switched off. Check the position of the battery main switch, if
necessary switch on..
Battery voltage not sufficient. Check that connection is firm and whether corrosion
has occurred..
Starting current fault. The voltage of full batteries fall to a maximum of 11V.
The wiring is severed if the voltage does not drop. The
battery is discharged if the voltage drops further.
MOTOR TURNS OVER BUT DOES NOT START
Cause Solution
Stop solenoid valve not opening. Check wire connections and circuitry to solenoid valve.
(ref. DC wiring diagram: Relay K2, Fuse)
Fuel pump does not operate. Check fuel-filter and pump: clean if necessary.
Lack of fuel. Check fuel supply.
Glow-plugs not working correctly. Check glow plugs and heating time.