Warnings and error messages
30.10.12 Chapter 13: Warnings and error messages - Page 155
Error messages can be acknowledged with the Start/Stop button, The controller will then return to stand-by mode.
13.2.2 Warning and fault thresholds
The threshold values resulting in triggering warnings and faults depend on the generator type and are compiled in
table 2-3.
Fig. 13.2.2-1: Warning and fault thresholds for different generator types
STARTING FAILS Generator start has failed
UNEXPECTED STOP Generator stopped unexpectedly
FAULT: OILPRESS Oil pressure error
BATTERY LOW Battery power too low
Inverter overtime Inverter temperature too high
Inverter overload Generator was overloaded, message is also issued when the generator output cable
is not connected to the inverter
INIT FAILED! Parameters were not correctly adopted into the EEPROM when the generator type was
initialised. Generator type must be reset.
„OUT“ is output instead of a temperature „Out of range“ - broken cable on corresponding temperature sensor
Generator type Warning/fault Warning threshold Fault threshold
5000i Marine Cylinder head temperature
Delay
85 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
70 °C
1 s
75 °C
1 s
5000i Fahrzeug (vehicle) Cylinder head temperature
Delay
90 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
100 °C
1 s
105 °C
1 s
P8000i Marine Cylinder head temperature
Delay
90 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
70 °C
1 s
75 °C
1 s
P8000i Fahrzeug (vehicle) Cylinder head temperature
Delay
90 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
100 °C
1 s
105 °C
1 s
P8-P50 Marine Cylinder head temperature
Delay
90 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
70 °C
1 s
75 °C
1 s
P8-P50 Fahrzeug (vehicle) Cylinder head temperature
Delay
95 °C
5 s
100 °C
5 s
Winding temperature
Delay
160 °C
5 s
165 °C
5 s
Error message on the display Meaning of error message