General operation
Seite/Page 196 Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation 22.3.11
The solder jumpers are marked on the printed circuit board (with jumper no. and at three-part solder jumper with soldering surface no.)
(1): Equivalent resistance for load control lamp e.g. for use with three-phase alternator also integrated automatic controller of Bosch. The resistance value is 68Ω 3W,
i.e. only for 12V.
(2): A closed contact switches the appropriate input to GND.
J209 1-2 DC-Control-Signal (-) = OK dynamo 12V at Kubota Z 482 / D 722 engines
2-3 DC-Control-Signal (+) = OK three-phase DC-alternator
J210 closed Input AC-Fault has Pull-Up-current
≥
10mA
open Input AC-Fault has Pull-Up-current
≥
2,5mA