MQTT2_EnableAlarmPost Activate the publication of alarms on the
dedicated topic.
The possible values are:
•0: Publication of alarms is disabled
•1: The publication of alarms is activated
and the concentrator remains in permanent
connection mode with the MQTT server.
Functional only for “mqtts_azure” type
MQTT2_
EnableInvokeMethod
Enable method calling. Allows the use of
dedicated topics.
The possible values are:
•0: Method call disabled
•1: Method call activated and the concentrator
remains in permanent connection mode with the
MQTT server.
Functional only for “mqtts_azure” type
MQTT2_Insecure Disable verication of the host name specied in
certicates.
The possible values are:
•0: Verication enabled
•1: Verication disabled.
Functional only for “mqtts” type
MQTT2_KeepAlive If no exchange made with the MQTT server for
the time dened in seconds, the concentrator
sends a ping to the MQTT server in order to
check the connection to it.
If the value is “0”, KeepAlive is disabled.
If the hub is in persistent connection mode with
the MQTT server and a disconnection is detected
after a KeepAlive, the hub will automatically
reconnect to the MQTT server.
10
MQTT2_KeyFile Name of the le including the private key specic
to the concentrator used for the connection. The
le is to be retrieved from your MQTT server and
must be imported to the concentrator by FTP or
by the web interface.
Works for all MQTT types except “mqtt”
MQTT2_Login Username to access the MQTT server.
Functional only for “mqtt” and “mqtts” types