INSTALLATION LOCATION
119 (3,000)
or more
40 (1,000)
or more
60
(1,500)
or more
11 (256) or more
(AUUB18,24)
12 (298) or more
(AUUB30,36)
71 (1,800)
or more
H
Strong and durable ceiling
Obstruction
Floor
H (The maximum height from oor to ceiling)
Model name AUUB18 AUUB24 AUUB30 AUUB36
Standard mode
118
(3,000)
118
(3,000)
125
(3,200)
125
(3,200)
High Ceiling mode
137
(3,500)
137
(3,500)
141
(3,600)
165
(4,200)
Unit : in. (mm)
NOTE:
Use the “Insulation kit for high humidity” (option), when the condition
under the roof is over 80% in humidity and over 30°C in temperature.
Otherwise, there is a risk of condensation on the ceiling.
4 Direction 3 Direction
4 (100)
or more
- (04-32) -
INDOOR
UNITS
INDOOR
UNITS