SIMPLE PROCEDURE FOR CREATING XIF AND REGISTER DATA
FOR NETWORK CONVERTOR (UTY-VLGX)
NOTE: For detail information, check the Application Manual which is included inside
packaged CD-ROM.
The following is the on-line procedure. It is also possible to create XIF &
Register Data o󰀨-line.
STEP 1: Connect the PC and Network Convertor (UTY-VLGX) .
Connection will be done by the connector cable provided as an accessory item of
UTY-VLGX.
STEP 2: Install Tool for Network Convertor (software) for UTY-VLGX in PC.
Tool for Network Convertor is the accessory item of UTY-VLGX.
STEP 3: Set Network Convertor (UTY-VLGX) to Installation Mode.
STEP 4: Setting ID number of UTY-VLGX on PC screen of Tool for Network Convertor.
(ID number is required to identify UTY-VLGX from BMS. A maximum of four Network
Convertors can be connected to one BMS, and ID number allocation is like 00, 01,
and so on.)
STEP 5: Initial setting of Indoor Unit & Outdoor Unit Addresses by using the Tool for Network
Convertor.
STEP 6: Register the initial setting data to UTY-VLGX. Click ‘Register’ dialog.
STEP 7: Set Conguration Properties.
To set the communication properties of UTY-VLGX, select the following communication
properties and types; otherwise, the default values will be used.
Select Communication items
-Event Driven communication or Cyclic communication.
(Default: Cyclic 3minutes)
-Communication Interval Time during turning ON all together.
(Default: 3 minutes)
Select Communication type (to communicate data with BMS)
- Communicate only when changing network variable or communicate all network
variable. (Default: Only when changing network variable)
- Communicate only when changing room temperature value.
(Default: Room temperature changed value 1.8°F (1°C))
STEP 8: Register the Conguration Properties data to UTY-VLGX. Click ‘Register’ dialog.
STEP 9: Making / Modifying XIF, and transfer XIF data by USB memory or oppy disk for
binding.
STEP 10: Reset Network Convertor (UTY-VLGX) to press ‘Reset SW7.
STEP 11: Turn OFF the power. After that, remove the connection of PC & Network Convertor
(UTR-VLGX) respectively.
In this stage, Network Convertor (UTY-VLGX) is ready for binding & commissioning.