SWITCH AND CONNECTOR ETC. LOCATION ON PCB
NOTE:
Ensure proper space for all connectors when mounted.
CAUTION:
Risk of explosion if battery is replaced by an incorrect type. Dispose of used
batteries according to the instructions.
IMPORTANT:
Tight the Power Supply and the LON cables to one of the 4 cable tie holes xed
to the casing with the plastic ties inside the BACnet
®
Gateway for VRF System. Do not use 2
holes to tie one cable.
Power Supply
Connect mains to the power supply connector as:
1.- Brown: Line (L)
2.- Yellow: Earth / Ground (E)
3.- Blue: Neutral (N)
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an
Ethernet CAT5 or higher cable.
VRF Network
Connect the LON bus to connectors A (-), B (+) and (SGND) of gateway’s PCB. Respect the
polarity.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication
between the Conguration Software and the gateway. Ethernet connection is also allowed for
conguration.
AC power fuse
VRF Network
connector
(LonWorks
®
)
BMS Network
connector
(Ethernet)
LED_PWR
LED_ERR
PC connector
(USB)
Battery for clock
- (05 - 160) -
CONTROL
SYSTEM
CONTROL
SYSTEM