Refrigerant circuit address setting
9) Pressing the SET BACK button, select a remote controller address (select the indoor unit
you want to operate).
Remote controller address
Ex.) When remote controller address “01” is
selected
*If the indoor unit you want to operate has already been selected, skip step 9)
10) Pressing the SET TIME < button or the SET TIME > button, display function number 02.
Function number
< : Down button
> : Up button
11) Pressing the SET TEMP. V button or the SET TEMP. Λ button, set up the refrigerant
circuit address data. (The setting range is from 00 to 99.)
Refrigerant circuit address data
Ex.) When refrigerant circuit address data “18” is
set up
12) Pressing the TIMER SET button, conrm the selected refrigerant circuit address data. (The
data will be transferred to the indoor unit.)
GOODERROR
When refrigerant circuit address data was
normally set up on the indoor unit
(Flashing display changes to illuminated display.)
When refrigerant circuit address data was not
set up on the indoor unit (-- is displayed.)
Set up refrigerant circuit address data again
according to the procedure in step 11) above.
- (07 - 26) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals