2-1-4. J-II series
SETTINGS LIST
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Remarks
0 0
Pipe length
setting
0 0
Standard (131 to
213ft.)
(40 to 65m)
l
Pipe length means the length between outdoor
unit and the nearest indoor unit.
0 1
Short (less than 131ft.)
(less than 40m)
0 2
Medium (213 to 295ft.)
(65 to 90m)
0 3
Long 1 (295 to 394ft.)
(90 to 120m)
0 4 Prohibited
1 0 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
1 1
Cooling
capacity shift
0 0 Normal mode
l
0 1 Save energy mode 1
0 2 High power mode 1
0 3 High power mode 2
0 4 Prohibited
1 2
Heating
capacity shift
0 0 Normal mode
l
0 1 Save energy mode
0 2 High power mode 1
0 3 High power mode 2
1 3 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
1 4 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
0 4 Prohibited
- (07 - 74) -
FUNCTION
SETTING
FUNCTION
SETTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Airstage J-II Series and is the answer not in the manual?

Fujitsu Airstage J-II Series Specifications

General IconGeneral
BrandFujitsu
ModelAirstage J-II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals