Function
Function
number
Setting number Default Details
*1 Auto
restart
40
00
Enable
Enable or disable automatic system restart after a power outage.
01
Disable
Cool Air
Prevention
43
00
Super low
Restrain the cold airow with making the airow lower when starting
heating operation. To correspond to the ventilation, set to 01.
01
Follow the setting
on the remote
controller
External
control
46
00
Start/Stop
Allow an external controller to start or stop the system, or to perform
an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
01
Emergency stop
02
Forced stop
Error
report
target
47
00
All
Change the target for reporting errors. Errors can either be reported in
all locations, or only on the wired remote.
01
Display only on
central remote
control
Fan setting
when cooling
thermostat OFF
49
00
Follow the setting
on the remote
controller
When set 00, Indoor unit is continued operation based upon Central
remote controller or individual controller set.
Once indoor unit received signal from External controller, Indoor unit
changed Fan mode forcibly.
When set 01, Indoor unit is continued operation based upon Central
remote controller or individual controller set.
Once indoor unit received signal from External controller, Indoor unit
stop forcibly.
Connection of the wired remote controller
(2-wire type or 3-wire type) and switching its thermistor are necessary.
01
Stop
*2 Switching
functions
for external
inputs and
external outputs
terminals
60
00
Mode 0
Set this function when connected to external devices such as the VRF
system ventilator, economizer, humidier, etc.
The connection terminal functions can be changed depending on
the type of external device. For details of the connection terminal
functions, refer to Chapter 8. 1-2. INDOOR UNIT.
01
Mode 1
02
Mode 2
03
Mode 3
04
Mode 4
05
Mode 5
06
Mode 6
07
Mode 7
08
Mode 8
Control
switching of
external heaters
61
00
Auxiliary heater
control 1
Sets the control method for the external heater being used. For details
of the control method, refer Chapter 8.
1-2-2. EXTERNAL OUTPUT.
01
Auxiliary heater
control 2
02
Heat pump
prohibition control
03
*3
Heater selection
control using
external
temperature 1
04
*3
Heater selection
control using
external
temperature 2
Operating
temperature
switching of
external heaters
62
00
Setting 0
Sets the temperature conditions when the external heater is ON.
For the temperature conditions, see "Temperature conditions when the
external heater is ON".
01
Setting 1
02
Setting 2
03
Setting 3
04
Setting 4
05
Setting 5
*1 : Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2 : Inappropriate setting may cause an external device malfunction. Conrm whether all the settings have been
performed appropriately according to the installing condition.
*3 : Only VR-II is setable.
- (07 - 113) -