Function
Function
number
Setting number Default Details
*1 Auto mode
type
68
00
Single
setpoint
auto
mode
(traditional)
Switch the setting method of auto mode to single or dual (cooling/
heating).
For heat pump systems, it is necessary to set the master indoor unit (by
wired remote controller).
01
Dual setpoint
auto
mode
*1 Deadband
value
69
00
0°C
Choose the minimum temperature between cooling and heating
settings (deadband) for Dual setpoint auto mode (set in No. 68).
01
0.5°C
02
1.0°C
03
1.C
04
2.0°C
05
2.5°C
06
3.0°C
07
3.5°C
08
4.0°C
09
4.5°C
*1 : Function number 68 and 69 will be usable provided that the corresponding operating device is connected.