2-12. TOUCH PANEL CONTROLLER
ADDRESS SETTING
Display the Installer Setting screen and press "Change" button of "1. Touch panel controller
address setting".
Select “Address” from 00 to 15 on the screen and click the button. At the end of setting, click
“OK” button.
NOTES:
Address No. can be set between "00" and "15". (Up to maximum 16 Touch Panel
Controller can be installed to 1 system).
When installing two or more Touch Panel Controller, set up so that Address No. does
not overlap.
Refer to the OPERATING MANUAL of Touch Panel Controller for details.
Keep Address No. of Touch Panel Controller from overlapping the controller (Central
remote controller, Network convertor for L
ON
W
ORKS
®
and Modbus
®
convertor
connected to the same VRF Network system)