SET3-1: Two-stage setting
Cooling setting temperature
(
u
...Factory setting)
SW
SET3-2
Cooling stage 1 setting
Temperature °F (°C)
Cooling stage 2 setting
Temperature °F (°C)
Remarks
u
OFF 68 (20) 64 (18) Pattern 1
ON 72 (22) 68 (20) Pattern 2
Heating setting temperature
(
u
...Factory setting)
SW
SET3-3
SW
SET3-4
Cooling stage 1 setting
Temperature °F (°C)
Cooling stage 2 setting
Temperature °F (°C)
Remarks
u
OFF OFF 81 (27) 86 (30) Pattern 1
OFF ON 77 (25) 82 (28) Pattern 2
ON OFF 75 (24) 79 (26) Pattern 3
ON ON 70 (21) 75 (24) Pattern 4
NOTES:
● Setting values are the limit temperature for cooling and heating.
● Energy saving performance is improved in the order from Cooling Pattern 1 to 2 and Heating pattern 1 to 4.
Delay OFF setting (SET2)
Delay OFF is the function to operate continuously even after reaching to the set temperature of
thermostat. This function may make air conditioning ecient.
Set the Delay OFF time by SW SET2-3 and SW SET2-4.
(
u
...Factory setting)
SW
SET2-3
SW
SET2-4
Delay o time
u
OFF OFF 0 minute
OFF ON 5 minutes
ON OFF 10 minutes
ON ON 20 minutes
Fun setting (Signal on terminal G) (SET2)
(
u
...Factory setting)
SW
SET2-1
SW
SET2-2
Indoor unit airow
u
OFF OFF AUTO
OFF ON HIGH
ON OFF MED
ON ON LOW