Upgrade and Maintenance Manual TX2560 M2 / RX2560 M2
Processor (CPU)
Ê
Carefully remove the defective CPU from its socket (2) in a vertical motion.
V CAUTION!
Be careful not to touch or bend the spring contacts on the CPU
socket.
Ê
Thoroughly clean residual thermal paste from the CPU surface using a lint-
free cloth.
Ê
Store the CPU in a save place for later reuse.
V CAUTION!
CPUs are extremely sensitive to electrostatic discharge and must be
handled with care. After a CPU has been removed from its protective
sleeve or from its socket, place it upside down on a nonconducting,
antistatic surface. Never push a CPU over a surface.
11.3.3 Installing the protective socket cover
Ê
Carefully lower the load plate over the CPU socket (see figure 269).
Ê
Fully fold back the socket release lever marked
Close 1st
until the bail on the
lever catches the latch on the load plate (see figure 270).
Ê
Close the socket release lever marked
Close 1st
and latch it under the load
plate retention tab (see figure 271).
Ê
Close the socket release lever marked
Open 1st
and latch it under the load
plate retention tab (see figure 272).