Chapter 2: Front panel programming
38 Vigilant VS1 and VS2 Technical Reference Manual
Default loop configuration settings
Loop class: Class B
• Zone
Type: Alarm
Correlation group: 001
Notes
- By default, NACs, zones, and most
devices are assigned to correlation
group 001.
- Relay and sounder bases with the
Follow option set to Head are not
automatically assigned to correlation
groups.
Event notification
Active > Printer: Yes
Active > Dialer: Acct 1
Active > NET: Yes
Active > CID: 110
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > NET: Yes
Trouble > CID: 373
Disable > Printer: Yes
Disable > Dialer: Acct 1
Disable > NET: Yes
Disable > CID: 570
Pre alarm > Printer: Yes
Pre alarm > Dialer: None
Pre alarm > NET: No
Pre alarm > CID: 118
Alarm verify > Printer: Yes
Alarm verify > Dialer: None
Alarm verify > NET: No
Alarm verify > CID: 118
Maintenance alert > Printer: Yes
Maintenance alert > Dialer: Acct 1
Maintenance alert > NET: Yes
Maintenance alert > CID: 393
Test > Printer: Yes
Test > Dialer: Acct 1
Test > NET: Yes
Test > CID: 614
• Device
Day sensitivity: Least
Night sensitivity: Least
Day prealarm %: Off
Night prealarm %: Off
Base follow: Alarm
Event notification
Active > Printer: Yes
Active > Coder: 00-00-00-00
Active > Dialer: Acct 1
Active > NET: Yes
Active > CID: 110
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > NET: Yes
Trouble > CID: 373
Disable > Printer: Yes
Disable > Dialer: Acct 1
Disable > NET: Yes
Disable > CID: 570
Pre alarm > Printer: Yes
Pre alarm > Coder: 00-00-00-00
Pre alarm > Dialer: None
Pre alarm > NET: No
Pre alarm > CID: 118
Type (input device): Depends on type of device
and marketplace
Type (output device): Genesis with audible/visible
silence
Correlation group: 1
Alarm verify > Printer: Yes
Alarm verify > Coder: 00-00-00-00
Alarm verify > Dialer: None
Alarm verify > NET: No
Alarm verify > CID: 118
Maintenance alert > Printer: Yes
Maintenance alert > Coder: 00-00-00-00
Maintenance alert > Dialer: Acct 1
Maintenance alert > NET: Yes
Maintenance alert > CID: 393
Test > Printer: Yes
Test > Coder: 00-00-00-00
Test > Dialer: Acct 1
Test > NET: Yes
Test > CID: 614