EasyManua.ls Logo

GE ALPS - Os Blocking

GE ALPS
366 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-38 ALPS Advanced Line Protection System
GE Power Management
2.3 PROTECTION SETTINGS 2 CALCULATION OF SETTINGS
2
2.3.18 OS BLOCKING
Out-of-step blocking (OSB) is offered as a standard feature in the ALPS. Refer to Section 1.4.4: OUT-OF-STEP BLOCK-
ING on page 1–14 for a complete description of the OSB logic. The OSB function is implemented through the distance
functions in the ALPS system as shown in Figure 2–13: TL5PICKUP / TL6PICKUP REPRESENTATION on page 2–35. For
an out-of-step condition, the apparent impedance seen by the relay will follow a typical swing line as shown below. The
ALPS recognizes an out-of-step condition by sensing that the MOB function operates first, and that the coordinating func-
tion (Zone 2, 3 or 4) operates a short time later. The MOBZONE setting is used to select which of the zones (Zone 2, 3 or
4) is used as the coordinating zone. Note that Zone 4 can only be used as the coordinating zone when it is set to look in the
forward direction (Z4DIRECTN = FORWRD).
Figure 2–14: OSB FUNCTION CHARACTERISTIC
Angles A, B and C are determined as a function of the reach (Zc) of the coordinating zone, the maximum load flow (mini-
mum Zload) and the fastest swing (first slip cycle). The angle A in the figure is selected via ZxPHARANG (x = 2, 3 or 4) and
determines the shape of the coordinating zone characteristic. Angle B is selected via the MOBCHARANG setting and
determines the shape of the MOB characteristic. Angle B should be set so the time for the fastest swing to traverse from
angle B to angle A is not less than 30 milliseconds. In addition, the A and B angle settings must be selected so that the dif-
ference between angles B and C is never less than 20°. Note that angle C is determined as a function of the minimum load
impedance (Zload) and the reach (Zc) of the coordinating zone. Load flow and stability studies may have to be run to deter-
mine the settings necessary to establish out-of-step blocking.
1601: MOBZONE - Coordinating Zone
Set MOBZONE to select a coordinating zone per the criteria described above.
1602: MOBCHARANG - MOB Characteristic Angle
Use the criteria described earlier to select an appropriate MOBCHARANG setting.
1603: BLOCKWHAT - Functions to Block during Out-of-Step Tripping
BLOCKWHAT is used to select which of the following are to be blocked during an out-of-step condition:
1. BLKALL - Block all tripping regardless of what operated to initiate the trip.
2. BLKDIST - Block tripping for operation of any of the distance functions.
3. BLKPHAS - Block tripping by any of the phase distance functions.
4. BLKNONE - allow tripping for any trip condition.
1604: BLOCKZ1 - Block All Zone 1 Functions
Set BLOCKZ1 = YES to block tripping by any of the Zone 1 distance functions, otherwise set BLOCKZ1 = NO.
1605: BLOCKZ2 - Block All Zone 2 Functions
Set BLOCKZ2 = YES to block tripping by any of the Zone 2 distance functions, otherwise set BLOCKZ2 = NO.
Swing Line
R
X
MOB
Zone 2, 3 or 4
Zload
A
C
Zc
B

Table of Contents

Related product manuals