2-64 ALPS Advanced Line Protection System
GE Power Management
2.5 REFERENCE TABLES 2 CALCULATION OF SETTINGS
2
2.5.3 GENERAL SETTINGS GUIDE
Table 2–12: GENERAL SETTINGS GUIDE (Sheet 1 of 2)
NO. MNEMONIC DESCRIPTION RANGE
(5A & 1A)
STEP DEFAULT
CONFIGURE
101 UNITID Unit ID 0000 to 9999 1 0000
102 SYSFREQ System Frequency 50 Hz, 60 Hz N/A 60Hz
103 PHASROTATE Phase Rotation ABC, ACB N/A ABC
104 TIMESYNCH Time Synch Source INTERNAL, IRIG-B N/A INTERNAL
105 NUM_BKR Number of Breakers 1, 2 N/A 1
106 NUM_TC Number of Trip Circuits 1, 2 N/A 1
107 NUM_MON Number of Trip Circuit Monitors for 1P trippin
:
format = abcdef;
for 3P trippin
:
format = abcd
a-f = 0 (on) or 1(off) 000111 (7)
T1 to T3 off
†
0000 (0)
T1 to T4 off
‡
108 DISPLAYVAL Value Display Mode PRI, SEC N/A SEC
109 LANGUAGE Lan
ua
e Option ENGLISH, SPANISH N/A ENGLISH
110 SYSIN1-4 System Inputs 1 to 4 0000 to 1111 (binary)
0 to 15 (decimal)
1 0000
COMMPORTS
201 COMPORT1 Communications Port #1
Settin
s
Baud Rate (xx), Parity
(y), Stop Bits (z)
format = xxyz
xx = 03, 12, 24, 48, 96;
y = 0 (none), 1 (odd), 2
(even);
z = 1, 2
9601
202 COMPORT2 Communications Port #2
Settin
s
Interface (i), Baud Rate
(xx), Parity (y), Stop Bits
(z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03, 12,
24, 48, 96; y = 0
(none), 1 (odd), 2
(even);
z = 1, 2
09601
203 COMPORT3 Communications Port #3
Settin
s
Interface (i), Baud Rate
(xx), Parity (y), Stop bits
(z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03, 12,
24, 48, 96; y = 0
(none), 1 (odd), 2
(even);
z = 1, 2
09601
204 PROTOCOL1 Communications Port #1
Protocol
GE-MODEM, ASCII,
DNP 3.0
N/A GE-MODEM
205 PROTOCOL2 Communications Port #2
Protocol
GE-MODEM, ASCII,
DNP 3.0
N/A ASCII
206 PROTOCOL3 Communications Port #3
Protocol
GE-MODEM, ASCII,
DNP 3.0
N/A GE-MODEM
OSC_GRAPHY
301 NUMFAULTS Number of Fault Records 2,4,8,12
(std. mem.)
6,12,24,36
(exp mem)
†
N/A 12
302 PREFAULT Number of Pre-fault Cycles 1 to 8 1 5
303 SPLITREC Splits Fault Record and
captures this percenta
e at end,
with 1-SPLITREC captured at
be
innin
0 to 100% 1 0
BRKR DUTY
401 EXPONENT
Exponent in
I
x
t
calculation
1.0 to 2.0 0.1 2.0
402 MAX_OP Maximum Number of Breaker
Operations for a Breaker
0 to 9999 1 0
† Applicable to the Sin
le Phase Trippin
model only.
‡ Applicable to the Three Phase Trippin
model only.
*
Contact converter output normally appears as a Lo
ic 1 with normally open contact connected; to invert output to Lo
ic 0, add 1000 to
the number.