1-10 ALPS Advanced Line Protection System
GE Power Management
1.3 CUSTOM PROGRAMMABILITY 1 PRODUCT DESCRIPTION
1
1.3.4 CONFIGURABLE OUTPUTS
All of the output relays in the ALPS, except for the alarm output relays, are user-configurable. However, each ALPS relay is
shipped with Default Output Relay Assignments. These are shown below and in Figure 1–28: ELEMENTARY DIAGRAM
WITH DEFAULT I/O (THREE PHASE TRIPPING) on page 1–50 for the three phase model and Figure 1–27: ELEMEN-
TARY DIAGRAM WITH DEFAULT I/O (SINGLE PHASE TRIPPING) on page 1–49 for the single phase model.
Table 1–5: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: SINGLE PHASE MODEL
RELAY DESCRIPTION MNEMONIC INDEX NO.
T1 TRIP BUS PHASE A TRIPA 33
T2 TRIP BUS PHASE A TRIPA 33
T3 TRIP BUS PHASE A TRIPA 33
T4 TRIP BUS PHASE A TRIPA 33
T5 TRIP BUS PHASE B TRIPB 34
T6 TRIP BUS PHASE C TRIPC 34
A1 MANUAL CLOSE BREAKER 1 MNCLS1 58
A2 MANUAL CLOSE BREAKER 2 MNCLS2 59
A3 TRIP BUS PHASE A TRIPA 33
A4 TRIP BUS PHASE A TRIPA 33
A5 THREE PHASE RECLOSE INITIATE RI-3P 37
A6 THREE PHASE RECLOSE INITIATE RI-3P 37
A7 RECLOSE CANCEL OUTPUT FROM SCHEME LOGIC CANCL 38
A8 to A12 UNASSIGNED --- ---
KT1 KEY TRANSMITTER 1 / CARRIER START #1 KEY1 39
KT2 KEY TRANSMITTER 2 / CARRIER STOP #1 KEY2 40
KT3 KEY TRANSMITTER 1 / CARRIER START #1 KEY1 39
KT4 KEY TRANSMITTER 2 / CARRIER START #2 KEY2 40
C1 NON-CRITICAL ALARM NCALM 52
C2 PT FUSE FAILURE ALARM FF 115
Table 1–6: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: THREE PHASE MODEL
RELAY DESCRIPTION MNEMONIC INDEX NO.
T1 TRIP CIRCUIT #1 TRIPA 33
T2 TRIP CIRCUIT #2 TRIPA 33
T3 TRIP CIRCUIT #3 TRIPA 33
T4 TRIP CIRCUIT #4 TRIPA 33
A1 MANUAL CLOSE CIRCUIT BREAKER #1 MNCLS1 58
A2 MANUAL CLOSE CIRCUIT BREAKER #2 MNCLS2 59
A3 BREAKER FAILURE INITIATE #1 TRIPA 33
A4 BREAKER FAILURE INITIATE #2 TRIPA 33
A5 RECLOSE INITIATE #1 RI_3P 37
A6 RECL OSE INITIATE #2 R1_3P 37
A7 RECLOSE CANCEL CANCL 38
A8 RECLOSE CANCEL CANCL 38
KT1 KEY TRANSMITTER 1 / CARRIER START #1 KEY1 39
KT2 KEY TRANSMITTER 2 / CARRIER STOP #1 KEY2 40
KT3 KEY TRANSMITTER 1 / CARRIER START #1 KEY1 39
KT4 KEY TRANSMITTER 2 / CARRIER START #2 KEY2 40
C1 NON-CRITICAL ALARM NCALM 52
C2 PT FUSE FAILURE ALARM FF 115