GE Power Management
ALPS Advanced Line Protection System 2-73
2 CALCULATION OF SETTINGS 2.5 REFERENCE TABLES
2
2.5.5 GENERAL SETTINGS DATA SHEETS
Table 2–14: GENERAL SETTINGS DATA SHEET (Sheet 1 of 2)
NO. MNEMONIC DESCRIPTION RANGE (5A & 1A) STEP USER SETTING
CONFIGURE
101 UNITID Unit ID 0000 to 9999 1
102 SYSFREQ System Frequency 50 Hz, 60 Hz N/A
103 PHASROTATE Phase Rotation ABC, ACB N/A
104 TIMESYNCH Time Synch Source INTERNAL, IRIG-B N/A
105 NUM_BKR Number of Breakers 1, 2 N/A
106 NUM_TC Number of Trip Circuits 1, 2 N/A
107 NUM_MON Number of Trip Circuit Monitors for 1P trippin
:
format = abcdef;
for 3P trippin
:
format = abcd
a-f = 0 (on) or 1(off)
108 DISPLAYVAL Value Display Mode PRI, SEC N/A
109 LANGUAGE Lan
ua
e Option ENGLISH, SPANISH N/A
110 SYSIN1-4 System Inputs 1 to 4 0000 to 1111 (binary)
0 to 15 (decimal)
1
COMMPORTS
201 COMPORT1 Communications Port #1
Settin
s
Baud Rate (xx), Parity
(y), Stop Bits (z)
format = xxyz
xx = 03, 12, 24, 48, 96,
19;
y = 0 (none), 1 (odd), 2
(even);
z = 1, 2
202 COMPORT2 Communications Port #2
Settin
s
Interface (i), Baud Rate
(xx), Parity (y), Stop Bits
(z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03, 12,
24, 48, 96, 19; y = 0
(none), 1 (odd), 2
(even);
z = 1, 2
203 COMPORT3 Communications Port #3
Settin
s
Interface (i), Baud Rate
(xx), Parity (y), Stop bits
(z)
format = ixxyz
i = 0 (RS232), 1
(RS485); xx = 03, 12,
24, 48, 96, 19; y = 0
(none), 1 (odd), 2
(even);
z = 1, 2
204 PROTOCOL1 Communications Port #1
Protocol
GE-MODEM, ASCII N/A
205 PROTOCOL2 Communications Port #2
Protocol
GE-MODEM, ASCII N/A
206 PROTOCOL3 Communications Port #3
Protocol
GE-MODEM, ASCII N/A
OSC_GRAPHY
301 NUMFAULTS Number of Fault Records 2,4,8,12
(std. mem.)
6,12,24,36
(exp mem)
†
N/A
302 PREFAULT Number of Pre-fault Cycles 1 to 8 1
303 SPLITREC Splits Fault Record and
captures this percenta
e at end,
with 1-SPLITREC captured at
be
innin
0 to 100% 1
BRKR DUTY
401 EXPONENT
Exponent in
I
x
t
calculation
1.0 to 2.0 0.1
402 MAX_OP Maximum Number of Breaker
Operations for a Breaker
0 to 9999 1
403 MAX_IXT Maximum Breaker Duty for a
Breaker
0 to 9999999 A
x
sec.
100
† Applicable to the Sin
le Phase Trippin
model only.
‡ Applicable to the Three Phase Trippin
model only.
* Contact converter output normally appears as a Lo
ic 1 with normally open contact connected; to invert output to Lo
ic 0, add 1000 to
the number