C-2 ALPS Advanced Line Protection System
GE Power Management
C.2 DEVICE PROFILE APPENDIX C
C
C.2 DEVICE PROFILE C.2.1 DNP V3.00 DEVICE PROFILE DOCUMENT
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name
: General Electric Power Mana
ement Inc.
Device Name
: ALPS Advanced Line Protection System
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
p Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is
described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Binary Counter (Object 20, Variations 5 and 6)
Frozen Counter (Object 21, Variations 5 and 6)
Analo
Input (Object 30, Variations 1, 2, 3 and 4)
Analo
Input Chan
e (Object 32, Variations 1, 2, 3 and 4)
Analo
Output (Object 40, Variations 1 and 2)
Analo
Output Block (Object 41, Variation 1)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
None
p
Fixed
p
Confi
urable
Maximum Application Layer Re-tries:
None
p
Confi
urable
Requires Data Link Layer Confirmation:
Never
p
Always
p
Sometimes
p
Confi
urable
Requires Application Layer Confirmation:
p
Never
p
Always
p
When reportin
Event Data
When sendin
multi-fra
ment responses
p
Sometimes
p
Confi
urable
Timeouts while waiting for:
Data Link Confirm None
p
Fixed
p
Variable
p
Confi
urable
Complete Appl. Fra
ment None
p
Fixed
p
Variable
p
Confi
urable
Application Confirm
p
None Fixed at 5000 ms
p
Variable
p
Confi
urable
Complete Appl. Response None
p
Fixed
p
Variable
p
Confi
urable
Others: (None)
S
S
S
S
S
S
S
S
S